BPE Make 300 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer

GTX33300L50
  • UPS System / Industrial UPS
Rs.3489000.4Rs.1888000
Add to cart
Item Catalogue
GTX-Series-160-600kVA-Catalogue ( Download )
pdf
Output Specification
Output Capacity (KVA )
300 KVA
Output Capacity (KW )
270 KW
Output Power Factor
0.99 Power Factor
Output Phase
3 Phase
Other Output Phase
Or Phase
Output Voltage
400 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
>0.99 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
< 3% linear load and <5% non-linear load
Transfer Time
<0 ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
UPS Parallel Upto
Optional
Input Specification
Input Voltage
400 Volt
Other Input Voltage
380 - 415 Volt
Input Phase
3 Phase
Other Input Phase
- Phase
Input frequency
50 Or 60 Hz
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
150 - 342 Volt
Input voltage range for main operations
342 - 477 Volt
Input Power Factor
>0.99 Power Factor
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Fuse
Input Voltage THD
<3 %
Input Short Circuit Current (Maximum)
kAmps.
Input Current (Maximum)
Amp.
Batteries & Runtime
Battery Position Option
External
Battery Circuit Breaker
Approved Battery Capacity (AH)
150 - 200 Amp.
Battery DC Bus
576 - 600 VDC
Battery Type Compatibility
Sealed Maintenance Free (SMF) / Valve Regulated Lead Acid (VRLA) type, Flooded / tubular / vented type
Communication & Management
Control panel
Touch Screen LCD User Interface
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
E3M_ColdStart, E3M_parallel, E3S_TempSensor
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
Decibal
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
- Meters
Storage Temperature
-25 - 55 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
- Meters
Online thermal dissipation
Btu/Hr
Protection Class
IP20
Compliances
Compliance
BIS
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Other Environmental Compliance
Compliant
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes
Physical
Maximum Height
1790 Mm
Maximum Width
850 Mm
Maximum Depth
1480 Mm
Shipping Height
Mm
Shipping Width
Mm
Shipping Depth
Mm
Net Weight
700 Kg
Shipping weight
Kg
Colour
Black
No addition Service required.
Item Image Item Name Model No. Total Price
Item Image Item Name Model No. Total Price
BPE Make Paralleling Kit for 3 Phase UPS

BPEPK03

Rs.53100

BPE Make SNMP Card for 3 Phase On Line UPS

BPESNMP03

Rs.53100

Item Image Item Name Model No. Total Price
BPE Make 300 KVA 3:3 Phase On-Line UPS with 8-10 Minutes Back up

Rs.3804728

Grade
By NJD 2015-10-07 00:00:00

Just as good as name brand UPS .

Work great. No complaints.

Grade
By charles lobel 2016-03-03 00:00:00

Five Stars

Excellent Product

Grade
By Nicole B. 2017-07-01 00:00:00

Great for my insulin pump!

I use these in my insulin pump. I have noticed that when I buy a larger quantity of UPS , I usually get a few duds. Not with these! Every single one has worked!

Grade
By sassy 2017-03-04 00:00:00

great price

glad to have these--always need a battery for something

Grade
By Michael Johnson 2015-03-11 00:00:00

WILL NOT RECOMMEND nor BUY AGAIN

UPS have a very SHORT LIFE WILL NOT RECOMMEND nor BUY AGAIN..

Product Options Available with BPE Make 300 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer - GTX33300L50